HOMEPAGE | ELECTRICAL REFERENCES | FAVORITE INTERNET LINKS | HVAC/R | APPLIANCES | SAFETY PAGE | FEEDBACK
Return to Reference Page

Electrical Circuits

	My definition of an electrical system is:
		
		A group of electrical circuits designed to safely
	provide electric power to any anticipated loads in that system.

	The circuits should be installed in a safe workman like manner.
	

	Section 215-2(b) FPN No. 2. Conductors for feeders as
defined in Article 100, sized to prevent a voltage drop exceeding 3 percent
at the farthest outlet of power, heating, and lighting loads, or combinations
of such loads, and where the maximum total voltage drop on both feeders
and branch circuits to the farthest outlet does not exceed 5 percent, will 
provide reasonable efficiency of operation. 


	Each branch circuit must meet NEC requirements in determining
the computed loads:

	Sections 220–3(a), 220–10(b), and 384–16(c). The NEC 
requires the branch circuit computed load for conductor sizing to be sized 
at 125% of the continuous load, plus the noncontinuous load (100%).


	The general lighting load is first computed at 3 volt-amperes per 
square foot of outside area not including the garage or porches. 

	Table 220–3(b), general use receptacles not greater than 
20 amperes are included in the 3 VA per foot of the general lighting load.

	The number of receptacles in the system are determined by the 
 locations of the receptacles. Each receptacle is rated at 180 va. A 
 receptacle must be located within 6 feet of any wall area measured along 
 the baseboard including around corners. This means the cord of an appliance
 in the center of a 12 foot span would be able to reach a receptacle either
 direction. There must be a receptacle within any wall space 2 foot of more.
 There must be a ground fault receptacle in any bathroom. There must be 
 ground fault receptacles within any 4 feet of kitchen counter top and do
 not install face up. There must be two ground fault receptacles outside,
 one in front and one in back. There must be one ground fault receptacle 
 in the garage area. There must be one receptacle circuit in the utility 
 room for the washer.

Branch Circuit Calculations:

	Section 220–3(c)(6). The NEC does not have a specific rule
 that says 10 receptacles on a 15 ampere circuit or 13 receptacles on
 a 20 ampere circuit. For 15 ampere circuits, the calculation is as follows:
 120 volts x 15 amperes = 1800 VA/180 VA = 10 receptacles, and for 20 ampere
 circuits, 120 volts x 20 amperes = 2400 VA/180 VA = 13 receptacles.
 
	There are many Articles that apply to branch circuits, such as
 210; Overcurrent Protection, 240; Wiring Methods, 300; Conductors, 310;
 Appliances, 422; Electric Space Heating Equipment, 424; Motors, 430; 
 and Air-Conditioning, 440.

 A summary of Article 220 branch circuit rules is as follows:


 
There are many Articles that apply to branch circuits, such as 210; Overcurrent Protection, 240; Wiring Methods, 300; Conductors, 310; Appliances, 422; Electric Space Heating Equipment, 424; Motors, 430; and Air-Conditioning, 440. Article 225 covers outside circuits: Article 225 contains the following requirements: A readily accessible disconnect is required at the remote building, located either outside or nearest the point of entrance inside [225–8]. There shall be no more than six disconnects mounted in a single enclosure, or up to six separate enclosures [230–71]. The disconnects must be grouped and each disconnect must be marked to indicate the load served [110–22 and 230–72]. Article 225 does not contain any requirements for grounding, but Section 250–24 contains the requirements for remote buildings and structures. The basic rule is that a ground wire is not required if the grounded conductor (neutral) is used to ground the separate building disconnect. However, a ground wire is permitted to the separate building. Article 225 contains the same requirements for outside overhead conductors as Article 230 for overhead service conductors: The minimum clearance for the point of attachment is 10 feet but it may need to be higher to maintain the minimum clearances specified in 225–18 [225–16]. Overhead conductors must maintain clearances from ground and roofs according to Sections 225–18 and 225–19. Top of Page